Regul R600 PLC

Regul R600 is a high-availability real-time programmable logic controller, designed for the use in process industries, where additional electromagnetic protection is preferred.

APPLICATIONS

  • High-availability process control systems for:
    • Steam and gas turbines (control and emergency protection)
    • Oil pumping stations and gas compressors
    • Main and auxiliary systems at power stations
    • Fire and gas systems
    • Water management systems
  • Fiscal applications (for example, LACT units)

General features

  • Real-time programmable logic controller
  • Modular configuration, allowing flexible extension and change of configuration
  • Supports up to 130,000 channels
  • Improved electromagnetic protection of the controller and enclosure of the modules, protective module form factor
  • In-module event archiving

Processing power and redundancy

  • Minimum application cycle time – 1 ms (5 ms with redundancy)
  • Scan time – 1 ms
  • Switchover in maximum two cycles
  • Processing of complex algorithms with powerful CPU modules and built-in microprocessors in I/O modules

System configuration

  • Up to 12 modules in a rack, up to 255 racks, up to 10 km (via fiberoptic line) between racks
  • RJ-45, SFP, or mixed connection between racks
  • Star, ring, or mixed network topologies
  • CPU module can be placed into any rack

Programming and visualization

  • Programming in Epsilon LD software with IEC 61131-3 languages + CFC
  • Online application update
  • Remote configuration/maintenance and application updates
  • Special firmware with MySQL database server
  • CPU module with DVI output for connecting a display and using Target-visualization
  • Web visualization option in CPU modules
Minimum application cycle time1 ms (5 ms in redundant configuration)
Scan time1 ms
Switchover time from main to standby controller5 ms
Timing accuracy 50 µs
ProcessorIntel Atom
RAM2 Gb
SSD4 Gb (optional up to 64 Gb)
Mean time between failures (MTBF) for a controller module>150,000 hours
Input power 85…264 VAC 18…36 VDC
120…370 VDC
I/O module size (W x H x D)30 х 267 х 186 mm
Operating temperature range -40…+60°С
ApprovalsCE, EAC, GOST-R, FCC-ready

Supported interfaces

  • RS-232 (9-pin, full duplex, speed 300–115200 bps, opto-isolation 500/1500 V, overvoltage protection)
  • RS-422/RS-485 (9-pin, speed 300–115200 bps, full-channel opto-isolation 500/1500 V, overvoltage protection) – up to 96 ports per controller
  • Ethernet 10/100/1000 RJ-45 (full duplex) – up to 4 ports per CPU
  • Ethernet 10/100/1000 FO (single-mode, multi-mode) – up to 2 ports per CPU

Supported communication protocols*

  • IEC 61870-5-101 (master/slave)
  • IEC 61870-5-104 (master/slave)
  • Modbus RTU (master/slave, with expansion capabilities)
  • Modbus TCP (master/slave, with expansion capabilities)
  • OPC DA, OPC UA
  • EtherCAT

*Additional communication protocols, including nonstandard ones, can be implemented according to your requirements.

  • Hot swapping of all modules
  • Hot-standby CPU modules
  • Dual ring high-speed internal data bus
  • Automatic power distribution between power supply modules
  • Redundancy of CPU, CPU interconnection, I/O modules, power supply modules, SCADA connection
  • Hybrid counter/digital modules with support of 2oo3 voting at the level of modules
R600 Mirror Redundancy

R600 Mirror Redundancy

R600 CPU and Power Redundancy

R600 CPU and Power Redundancy

R600 Redundant I/O and Bus

R600 Redundant I/O and Bus

R600 Shared I/O Dual Ring

R600 Shared I/O Dual Ring

Part numberDescriptionChannels (ports)
CPU MODULES
CU 00 052Central processor unit, CPU module
• Redundancy support
• Intel Atom
• 2 GB RAM, 1 × 4 GB SSD
• 1 × RS-232, 1 × RS-485
• 4 × Ethernet RJ-45
• GPS/GLONASS receiver

CU 00 052 (W) additionally includes web server with support of Web visualization
CU 00 062Central processor unit, CPU module
• Redundancy support
• Intel Atom
• 2 GB RAM, 1 × 4 GB SSD
• 1 × RS-232, 1 × RS-485
• 2 × Ethernet RJ-45, 2 × Ethernet SFP
• GPS/GLONASS receiver

CU 00 062 (W) additionally includes web server with support of Web visualization
CU 00 072Central processor unit, CPU module
• Redundancy support
• Intel Atom
• 2 GB RAM, 1 × 4 GB SSD
• 1 × RS-232, 1 × RS-485
• 2 × Ethernet RJ-45, 2 × Ethernet SFP
• 1 × DVI, 2 × USB host
• GPS/GLONASS receiver

CU 00 072 (W) additionally includes web server with support of Web visualization
POWER SUPPLY AND BUS EXTENSION MODULES
PP 14 011Power supply module 24 V DC, 75 W
• Redundancy support
• Bus extension ports (IN, OUT), RJ-45
PP 14 021Power supply module 24 V DC, 75 W
• Redundancy support
• Bus extension ports (IN, OUT), SFP
PP 14 031Power supply module 220 V AC/DC, 75
• Redundancy support
• Bus extension ports (IN, OUT), RJ-45
PP 14 041Power supply module 220 V AC/DC, 75 W
• Redundancy support
• Bus extension ports (IN, OUT), SFP
COMMUNICATION
MODULES
CP 04 011Communication processor RS-485 (Modbus RTU, IEC-61870-5-101, user protocols), 4 ports4
ANALOG MODULES
AI 16 011Analog input, AI module (current)
• Current measuring range: 0…20 mA, 4…20 mA
• 16 channels
• Resolution: 14 bits (including overflow)
• Measurement error under normal conditions: ±0.1%
• Common galvanic isolation
16
AI 08 021Analog input, AI module (current, HART)
• Current measuring range: 0…20 mA, 4…20 mA
• 8 channels
• Resolution: 16 bits (including overflow)
• Measurement error under normal conditions: ± 0.1%
• Built-in HART protocol
• 1 ADC and 1 HART-modem for each channel
• Channel galvanic isolation
8
AI 08 031Analog input, AI module (thermal resistances, thermocouples)
• Thermal resistance measurement range: 1…450 Ohm
• 8 channels
• Supported thermal resistances: Cu50, Cu100, Pt50, Pt100, Ni50, Ni100
• Supported thermocouples: R, S, B, J, T, E, K, N, A-1, A-2, A-3, L
• Resolution: 24 bits (including overflow)
• Measurement error under normal conditions: ±0.1%
• Common galvanic isolation

8
AI 08 041Analog input, AI module (current, voltage; high-accuracy)
• Current measuring range: 0…20 mA, 4…20 mA
• Voltage measuring range: 0…+10 V, -10…+10 V
• 8 channels
• Resolution: 16 bits (including overflow)
• Measurement error under normal conditions: ±0.025%
• Channel galvanic isolation
• Individual ADC for each channel
8
AO 08 011Analog output, AO module (current)
• Output range, current: 0…20 mA, 4…20 mA
• 8 channels
• Resolution: 16 bits
• The error of the formation of the control signal under normal conditions: ±0.1%
• Channel galvanic isolation
8
AO 08 021Analog output, AO module (current, HART)
• Output range, current: 0…20 mA, 4…20 mA
• 8 channels
• The error of the formation of the control signal under normal conditions: ±0.1%
• Built-in HART protocol
• Channel galvanic isolation
8
DIGITAL MODULES
DI 32 011Digital input, DI module
• Input current: 24 VDC
• 32 channels (4 groups by 8 channels)
• Group galvanic isolation
32
DO 32 011Digital output, DO module
• Output current: 24 VDC / 0.5 A
• 32 channels (4 groups by 8 channels)
• Group galvanic isolation
32
COUNTER MODULES
DA 03 011Counter/digital module
• Channel supply voltage: 3, 5, 12, 24 V
• Frequency measurement range: 1 Hz … 500 kHz
• Frequency generation range: 1 Hz … 10 kHz
• Pulse measurement range: 1…264 (with overflow)
• Frequency measurement error under normal conditions: less than ± 0.01%
• Pulse-counting error: ±1 pulse
• 3 × counter channels
• 1 × generator channel
• 6 × DI channels, 24 V
• 6 × DO channels, 24 V / 0.5 A
• Channel galvanic isolation of the counter channels
3/1/6/6
DA 03 022Counter/digital module
• Channel supply voltage: 5, 12, 24 V
• Frequency measurement range: 1 Hz … 500 kHz
• Frequency generation range: 1 Hz … 10 kHz
• Pulse measurement range: 1…264 (with overflow)
• Frequency measurement error under normal conditions: less than ± 0.01%
• Pulse-counting error: ±1 pulse
• 3 × counter channels
• 1 × generator channel
• 6 × DI channels, 24 V
• 6 × DO channels, 24 V / 0.5 A
• Built-in software for electronic overspeed trip
• Support of magnetic RPM sensor
• Channel galvanic isolation of the counter channels
3/1/6/6
CHASSIS
CH 07 011Chassis with 7 slots (1 PP and 5 expansion slots)
CH 14 011Chassis with 14 slots (1 PP and 12 expansion slots)
OTHER
OO 00 000Empty module (slot cover)

SOFTWARE
Epsilon LD – programming and configuration software

MANUALS
To receive the manuals, please, send us a request with the button “Ask for manuals” above. Will be delivered to your e-mail address.

Regul R600 System Manual (DPA-309, v2.12)
Redundancy Manual (DPA 302.4)

Epsilon LD User Manual (DPA-302, v2.1)
Epsilon LD IEC-104 User Guide
Epsilon LD Modbus User Guide
Epsilon LD HART User Guide

CERTIFICATES
EC Declaration of Conformity

Overall and Installation Dimensions

Overall and Installation Dimensions of PLC Regul R600

Please leave your contact details below and our manager will contact you shortly.

Name:*
E-mail:*
Phone:
Company:
Message:
Please, confirm you are not a robot:
×

To receive a download link to the manuals, please, provide your contact details

Name:*
E-mail:*
Word Verification:
×

To download the file, please, leave your contact details in the form below.

By using this form you agree with the storage and handling of your data by this website.

×
Subscribe to updates

To subscribe to updates, please, provide your contact details

Name:*
E-mail:*
Word Verification:
×