Can I use fiberoptics with Regul controllers?

0 Comment

Yes, single-mode and multi-mode. The choice of cables between the racks depends on the rack extension modules, ST XX. You can also combine copper cable on one side of the rack and fiberoptic cables on another.

CPU synchronization can be done over copper or fiberoptic cables. Just both CPU modules need to have ports for fiberoptic connection in the latter case. Same applies to SCADA connection.

The limitation is that there are two ports for fiberoptic connection, so in case of redundant CPU sync and redundant SCADA connection, you have to select which one uses copper.